V/LNV - Series
Suitable for firetube, watertube and cost iron boilers; the V series features a unique aerodynamic air damper design which permits accurate air-to-fuel settings for maximum combustion efficiency. The standard V series offers natural gas, propane gas, pressure atomized #2 oil and combination gas/oil fuel options at capacities from 1,300,000 to 16,800,000 Btu/hour. The low NOx V series offers natural gas, propane gas, pressure atomized #2 oil, and combination gas/oil fuel options at capacities from 1,300,000 to 14,700,000 Btu/hour. Through the use of advanced technology, the V series offers high turndown up to 10:1 on natural gas, and low emission capabilities with turndown up to 5:1.
|
Capacities and Specifications
| Burner Size |
13 |
15 |
17 |
20 |
21 |
25 |
| Frame Size |
1 |
1 |
1 |
1 |
1 |
1 |
| Gas Input (Mbtu/hr) |
1,300 |
1,500 |
1,700 |
2,000 |
2,100 |
2,500 |
| Oil Input (U.S. gph) |
9.3 |
10.7 |
12.1 |
14.3 |
15.0 |
17.9 |
| Boiler Horsepower |
31 |
36 |
40 |
48 |
50 |
60 |
| Blower Motor Horsepower |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
| Remote Oil Pump Motor Horsepower |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
| Furnace Pressure ("w.c.) |
0.5 |
0.6 |
0.7 |
1.0 |
1.1 |
1.4 |
| Standard Gas Train Pipe Size (in.) |
1 |
1 |
1 |
1 |
1 |
1-1/2 |
| Gas Pressure Required (PSI) |
9.2 |
11.7 |
14.7 |
20.2 |
22.1 |
10.4 |
| FGR Line Piping(in.) |
4 |
4 |
4 |
4 |
4 |
4 |
| Shipping Weight (lbs) |
550 |
550 |
550 |
550 |
550 |
550 |
| Burner Size |
30 |
34 |
35 |
40 |
42 |
45 |
50 |
| Frame Size |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
| Gas Input (Mbtu/hr) |
3,000 |
3,400 |
3,500 |
4,000 |
4,200 |
4,500 |
5,000 |
| Oil Input (U.S. gph) |
21.4 |
24.3 |
25.0 |
28.6 |
30.0 |
32.1 |
35.7 |
| Boiler Horsepower |
71 |
81 |
83 |
95 |
100 |
107 |
119 |
| Blower Motor Horsepower |
2 |
3 |
3 |
3 |
3 |
3 |
3 |
| Remote Oil Pump Motor |
1/3 |
1/3 |
1/3 |
1/3 |
1/3 |
1/3 |
1/3 |
| Furnace Pressure ("w.c.) |
1.5 |
1.9 |
2.0 |
1.4 |
1.5 |
1.6 |
2.0 |
| Standard Gas Train Pipe Size (in.) |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
| Gas Pressure Required (PSI) |
8.7 |
10.3 |
8.1 |
10.4 |
11.5 |
10.8 |
13.6 |
| FGR Line Piping (in.) |
4 |
4 |
4 |
4 |
4 |
4 |
4 |
| Shipping Weight (lbs) |
600 |
600 |
700 |
700 |
700 |
700 |
700 |
| Burner Size |
54 |
55 |
60 |
63 |
70 |
80 |
84 |
90 |
| Frame Size |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
| Gas Input (Mbtu/hr) |
5,400 |
5,500 |
6,000 |
6,300 |
7,000 |
8,000 |
8,400 |
9,000 |
| Oil Input (U.S. gph) |
38.6 |
39.3 |
42.9 |
45.0 |
50.0 |
57.0 |
60.0 |
64.3 |
| Boiler Horsepower |
129 |
131 |
143 |
150 |
167 |
190 |
200 |
214 |
| Boiler Motor Horsepower |
5 |
5 |
5 |
5 |
7.5 |
7.5 |
7.5 |
10 |
| Remote Oil Pump Motor HP |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
1 |
1 |
| Furnace Pressure ("w.c.) |
2.4 |
2.5 |
3.0 |
2.0 |
2.5 |
3.2 |
3.5 |
4.0 |
>
| Standard Gas Train Pipe Size (in.) |
2 |
2 |
2 |
2 |
2 1/2 |
2 1/2 |
2 1/2 |
2 1/2 |
| Gas Pressure Required ("w.c.) |
19.2 |
19.7 |
17.6 |
19.4 |
15.8 |
15.0 |
15.5 |
15.5 |
| FGR Line Piping (in.) |
4 |
4 |
4 |
4 |
4 |
4 |
4 |
| Shipping Weight (lbs) |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
| Burner Size |
100 |
105 |
110 |
120 |
126 |
147 |
| Frame Size |
4 |
4 |
4 |
4 |
4 |
4 |
| Gas Input (Mbtu/hr) |
10,000 |
10,500 |
11,000 |
12,000 |
12,600 |
14,700 |
| Oil Input (U.S. gph) |
71.4 |
75.0 |
78.6 |
85.7 |
90.0 |
105.0 |
| Boiler Horsepower |
238 |
250 |
262 |
286 |
300 |
350 |
| Boiler Motor Horsepower |
15 |
15 |
15 |
15 |
15 |
15 |
| Remote Oil Pump Motor HP |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
| Furnace Pressure ("w.c.) |
3.2 |
3.4 |
3.6 |
4.2 |
4.8 |
4.8 |
| Standard Gas Train Pipe Size (in.) |
2.5 |
2.5 |
2.5 |
2.5 |
2 |
2 |
| Gas Pressure Required ("w.c.) |
20 1/2 |
44 5/7 |
48 5/7 |
34 1/5 |
49 1/9 |
2.5 PSI |
| FGR Line Piping (in.) |
6 |
6 |
6 |
6 |
6 |
6 |
| Shipping Weight (lbs) |
1,550 |
1,550 |
1,550 |
1,550 |
1,550 |
1,550 |
| Burner Size |
13 |
15 |
17 |
20 |
21 |
25 |
30 |
34 |
| Frame Size |
1.0 |
1.0 |
1.0 |
1.0 |
1.0 |
1.0 |
1.0 |
1.0 |
| Gas Input (Mbtu/hr) |
1,300 |
1,500 |
1,700 |
2,000 |
2,100 |
2,500 |
3,000 |
3,400 |
| Oil Input (U.S. gph) |
9.3 |
10.7 |
12.1 |
14.3 |
15.0 |
17.9 |
21.4 |
24.3 |
| Boiler Horsepower |
31 |
36 |
40 |
48 |
50 |
60 |
71 |
81 |
| Blower Motor Horsepower |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
2 |
3 |
| Remote Oil Pump Motor HP |
1/3 |
1/3 |
1/3 |
1/3 |
1/3 |
1/3 |
1/3 |
1/3 |
| Furnace Pressure ("w.c.) |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
1.5 |
| Standard Gas Train Pipe Size (in.) |
1 |
1 |
1 |
1 |
1 |
1-1/2 |
2 |
2 |
| Gas Pressure Required (PSI) |
9.2 |
11.7 |
14.7 |
20.2 |
22.1 |
10.4 |
8.7 |
10.3 |
| Shipping Weight (lbs) |
550 |
550 |
550 |
550 |
550 |
550 |
550 |
550 |
| Burner Size |
35 |
40 |
42 |
45 |
50 |
54 |
55 |
| Frame Size |
2.0 |
2.0 |
2.0 |
2.0 |
2.0 |
2.0 |
2.0 |
| Gas Input (Mbtu/hr) |
3,500 |
4,000 |
4,200 |
4,500 |
5,000 |
5,400 |
5,500 |
| Oil Input (U.S. gph) |
25.0 |
28.6 |
30.0 |
32.1 |
35.7 |
38.6 |
39.3 |
| Boiler Horsepower |
83 |
95 |
100 |
107 |
119 |
129 |
131 |
| Blower Motor Horsepower |
3 |
3 |
3 |
3 |
3 |
5 |
5 |
| Remote Oil Pump Motor HP |
1/3 |
1/3 |
1/3 |
1/3 |
1/3 |
3/4 |
3/4 |
| Furnace Pressure ("w.c.) |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
| Standard Gas Train Pipe Size (in.) |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
| Gas Pressure Required (PSI) |
8.1 |
10.4 |
11.5 |
10.8 |
13.6 |
19.2 |
19.7 |
| Shipping Weight (lbs) |
600 |
600 |
700 |
700 |
700 |
700 |
700 |
| Burner Size |
60 |
63 |
70 |
80 |
84 |
90 |
100 |
105 |
110 |
| Frame Size |
3.0 |
3.0 |
3.0 |
3.0 |
3.0 |
3.0 |
3.0 |
3.0 |
3.0 |
| Gas Input (Mbtu/hr) |
6,000 |
6,300 |
7,000 |
8,000 |
8,400 |
9,000 |
10,000 |
10,500 |
11,000 |
| Oil Input (U.S. gph) |
42.9 |
45.0 |
50.0 |
57.1 |
60.0 |
64.3 |
71.4 |
75.0 |
78.6 |
| Boiler Horsepower |
143 |
150 |
167 |
190 |
200 |
214 |
238 |
250 |
262 |
| Blower Motor Horsepower |
5 |
5 |
7-1/2 |
7-1/2 |
7-1/2 |
10 |
15 |
15 |
15 |
| Remote Oil Pump Motor HP |
3/4 |
3/4 |
3/4 |
3/4 |
1 |
1 |
1-1/2 |
1-1/2 |
1-1/2 |
| Furnace Pressure ("w.c.) |
3.5 |
3.5 |
3.5 |
3.5 |
3.5 |
3.5 |
3.5 |
3.5 |
3.5 |
| Standard Gas Train Pipe Size (in.) |
2 |
2 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
| Gas Pressure Required (PSI) |
17.6 |
19.4 |
15.8 |
15.1 |
15.5 |
17.4 |
20.5 |
44.7 |
48.7 |
| Shipping Weight (lbs) |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
800 |
| Burner Size |
120 |
126 |
147 |
| Frame Size |
4.0 |
4.0 |
4.0 |
| Gas Input (Mbtu/hr) |
12,000 |
12,600 |
14,700 |
| Oil Input (U.S. gph) |
85.7 |
90.0 |
105.0 |
| Boiler Horsepower |
286 |
300 |
350 |
| Blower Motor Horsepower |
10 |
15 |
15 |
| Remote Oil Pump Motor HP |
1-1/2 |
1-1/2 |
1-1/2 |
| Furnace Pressure ("w.c.) |
4.5 |
4.5 |
4.5 |
| Standard Gas Train Pipe Size (in.) |
2-1/2 |
2 |
2 |
| Gas Pressure Required (PSI) |
34.2 |
49.1 |
2.5 |
| Shipping Weight (lbs) |
1,550 |
1,550 |
1,550 |
Gas Based:
| Model |
Fuel |
| VG |
Gas |
| LNVG |
Gas |
|
Oil Based:
|
Gas/Oil Based:
| Model |
Fuel |
| VLG |
Gas/No. 2 Oil |
| LNVLG |
Gas/No. 2 Oil |
|
|