H - Series The H-Series Burners are designed to operate on gas, oil, or a combination of fuels at capacities ranging from 1,000,000 to 12,500,000 Btu/H. The H-Series Burners are designed for cast iron firebox or watertube boilers. The design of these units feature low CO performance, a unique air damper for easy combustion set-up independent low and high fire adjustment
.
|
Capacities and Specifications
| Burner Size |
10 | 13 | 15 | 17 |
20 | 21 | 25 |
| Oil Input (U.S. gph) |
7.2 | 9.3 | 10.7 | 12.1 |
14.2 | 15 | 17.8 |
| Gas Input (Btu/hr) |
1,000 | 1,300 | 1,500 | 1,700 |
2,000 | 2,100 | 2,500 |
| Boiler Horsepower |
24 | 31 | 36 | 41 |
48 | 50 | 60 |
| Blower Motor Horsepower |
1/2 | 1/2 | 1/2 | 1/2 |
1/2 | 3/4 | 3/4 |
| Shipping Weight (lbs) |
450 | 450 | 450 | 450 |
450 | 450 | 450 |
| Burner Size |
30 | 34 | 35 | 40 |
42 | 45 |
| Oil Input (U.S. gph) |
21.4 | 24.3 | 25 | 28.6 |
30 | 32.1 |
| Gas Input (Btu/hr) |
3,000 | 3,400 | 3,500 | 4,000 |
4,200 | 4,500 |
| Boiler Horsepower |
72 | 81 | 84 | 96 |
100 | 108 |
| Blower Motor Horsepower |
3/4 | 1 | 1 | 1-1/2 |
2 | 2 |
| Shipping Weight (lbs) |
500 | 500 | 500 | 600 |
600 | 600 |
| Burner Size |
50 | 54 | 55 | 60 |
63 | 70 | 80 | 84 | 90 |
| Oil Input (U.S. gph) |
35.7 | 38.6 | 39.3 | 42.9 |
45 | 50 | 57.1 | 60 | 64.3 |
| Gas Input (Btu/hr) |
5,000 | 5,400 | 5,500 | 6,000 |
6,300 | 7,000 | 8,000 |
8,400 | 9,000 |
| Boiler Horsepower |
119 | 129 | 131 | 143 |
150 | 167 | 191 | 200 | 215 |
| Blower Motor Horsepower |
2 | 3 | 3 | 3 |
5 | 5 | 5 | 5 | 7-1/2 |
| Shipping Weight (lbs) |
700 | 700 | 700 | 700 |
700 | 700 | 700 | 700 | 700 |
| Burner Size |
100 | 105 | 110 | 120 |
125 |
| Oil Input (U.S. gph) |
71.4 | 75 | 78.6 | 85.7 |
90 |
| Gas Input (Btu/hr) |
10,000 | 10,500 | 11,000 | 12,000 |
12,600 |
| Boiler Horsepower |
239 | 250 | 262 | 286 |
297.6 |
| Blower Motor Horsepower |
7-1/2 | 7-1/2 | 7-1/2 | 10 |
10 |
| Shipping Weight (lbs) |
1,100 | 1,100 | 1,100 | 1,450 |
1,450 |
Gas Based:
|
Oil Based:
|
Gas/Oil Based:
| Model |
Fuel |
| HLG | Gas/No. 2 Oil |
|
|
Notes:
- Firing rates based on 60 cycle and altitudes to 2000ft. above sea level. For impeller and motor sizes at higher altitudes, and 50 cycle applications, consult factory. Gas input based on 1000 Btu/cu. ft. and .60 specific gravity oil input based on 140,000 Btu/gal.
- Oil input based on No. 2 oil @ 140,000 Btu/gal
- Gas input based on Natural Gas @ 1,000 Btu/cu.ft and 0.60 specific gravity
- Capacity based on neutral tp 0.75" wc furnace pressure for model H10-25, neutral tp 1"wc for model H30-45, neutral to 2"wc for model H50-90, and furnace pressure upto 3"wc for model H100-120
- Boiler overall efficiency of 80% estimated. Industrial Combustion does not guarantee overall boiler efficiency.
|